Infinity’s designs are fully compliant with the Uptime Institute’s Tier III and Tier IV design specifications and can be further modified to meet customer specific requirements on resilience
Power & Efficiency
• Dual power feeds at 11kV or 33kV
• Standby generation and UPS systems (either diesel Rotary or conventional systems) are provided with generation supported as standard by 72 hours fuel storage
• IT load supported up to 2500 W per square metre as standard
• Plant and Halls designed to achieve a PUE of less than 1.4
Cooling
• 600-950mm plenum beneath raised floor (to client’s preference)
• Cooling redundancy to customer specification
• Variable with options of N+1, N+25% or N+2
• Central humidification system with water detection system[s]
• Cooling is matched to support planned IT loads in line with customer requirements, including optional additional cooling to support very high density needs
• Typically delivered as a hot aisle / cold aisle system
Building
• 24x7x365 managed building
• Highly secure with excellent loading facilities
• Floor loadings in excess of 10kN
